HV Hipot ad Xiangyang providere impetu voltage debugging pro Xiangyang Power Company

HV Hipot ad Xiangyang providere impetu voltage debugging pro Xiangyang Power Company

In August, post-venditio technici HV Hipot ad Xiangyang.Finis huius itineris erat ut impetus voltage debugging officia praeberet pro Xiangyang Power Supple Company.
Postquam ad locum perventum est, adiuvante et cooperatione emptoris, institutionem fulminis impulsum voltage generantis exercebit.

 

雷电 冲击 电压 发生器

 

 

De-site debugging de GDCY-400kV fulgur impetus voltage generantis
In-site pilam distantiam calibratiis: corpus pilae spatium calibratiis et SECURIS globus procul calibratiis (3000/200/ metiri)

工频 耐压

局 放仪

In-site cursus in test: 30KV positivus et negativus polaritas multiplex probat (congredi T1=1.2±30%/T2=50±20%us/TC=2 ad 6us)

回 路 电阻 测试仪

De-site vires test: 80% output rated voltage

 


De-site disciplina theoretica et operationalis:
Mos usu - simulata test product test: 10KV potentia transformer
1. plena undam test

 


Test requisita: test voltage 75KV, waveform time T1=1.2±30%/T2=50±20% nobis
Ager operatio: duo scaena voltage output utens
On-site modulation unda;
Resistentia capitis unda: 150Ω pro primo gradu, 500Ω pro secundo gradu (2 1KΩ in parallelo)
Unda resistentia caudae: 1st statio 45Ω, scaena 2nd 45Ω
Test operatio et waveform;
2. test cutoff

 


Test requisita: test voltage 85KV, unda caput temporis T1=1.2±30%, abscise tempus TC=2 ad 6us
Ager operatio: duo scaena voltage output utens
On-site modulation unda;
Resistentia capitis unda: Level 1 75Ω, Level 2 500Ω (2 1KΩ in parallelis)
Unda resistentia caudae: 1st statio 45Ω, scaena 2nd 45Ω
Test operatio et waveform;
Post hanc institutionis seriem, emptorem altissimam intelligentiam totius instrumenti habet, quod emptorem in ipsa operatione confidentiorem facit!


Post tempus: Aug-24-2022

Epistulam tuam nobis mitte;

Epistulam tuam hic scribe et mitte nobis