GDSF-411CPD SF6 Gas Comprehensive Analyzer
GDSF-411CPD SF6Gas comprehensive analyser est portable fabrica disposito ut metiretur SF6gas roris punctum, puritatis et compositionis productum.Media pars cum speculi frigido methodus adhibetur ad punctum ros probandum, sensorem Europaeum cum methodo infrarubra probandi SF.6gas puritatem et sensorem electrochemicum ex Membrapor ad probandum SF6Gas productum compositione.Praeterea nos quoque astulas professionales adhibemus et praestantes algorithmos STMicroelectronics programmatis.
SF6Umor
Modus mensurae | Speculum modum frigidum (Stirling Refrigeration) |
Mensurae range | Ros punctum -100℃--+20℃(90s unius punctum mensurae); Error: melius quam ± 0.2℃ |
Repetere facultatem | ± 0.1 |
Resolution | 0.01 |
Propono unitas | , ppm, P20(Converti ad valorem XX) |
SF6Puritas
Modus mensurae | Infrared mensurae principium (seriem sensoriis NDIR) |
range mensuræ | 0 ~ 100% SF6Error: melius quam ± 0.3% FS |
Responsio tempus | [90%] 60s |
Repeatability | ± 0.3% |
Resolution | 0.01% |
Propono unitas | % |
SF6Decomposition Products
Modus mensurae | Electrochemical mensurae principium (series electronica sensoriis ex Membrapor) |
Mensurae range | SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0~50ppmv |
Sagacitas | SO2: 10ppmv±3% H2S: 10ppmv±3% CO: 50ppmv ± 4% HF: 10ppmv±3% |
Repetere facultatem | SO2: 10ppmv±2% H2S: 10ppmv ± 2% CO: 50ppmv±2% HF: 10ppmv ± 2% |
Resolution | 0.01ppmv |
Propono unitas | ppmv |
General Parameters
Potentia copia | 220VAC±10%, 50Hz, AC/DC usus, operatio continua plus quam 8 horas est. |
Usus environment temperatus | -20--+60℃ |
Environment humiditas | 90% RH |
Mensurae valorem influentiam | Nullus effectus pressura et fluxus |
Dimension | 570*420*280mm |
Pondus | Non plus quam 20kg. |
Principalis Tester | Pars I |
adaptor | 1 set |
Teflon pipe (include valvae fluxus commensuratio et iungo ieiunium) | 1 set |
Cauda tibia | 1 set |
Parce partes | 1 set |
Patina | Pars I |
User's Guide | Pars I |
Fama test | Pars I |