GDSF-311WPD 3-In-1 SF6 Gas Analyzer
GDSF-311WPD (GDSF-411WPD) instrumentum ideale est cum necessarium est ut aqua contenta, puritas et compositione productorum gasorum SF6 probentur.Componentes nuclei rosi punctum testium DRYCAP® est series sensoriorum a comitatu Finniae Vaisala producta.Principium ultrarubrum SF6 puritatis gasi probatio sensorem factorum ab Company Sensore Europaeo puritatem gasi SF6 probare adhibetur.Sensorem electrochemicum a Mombabo Societati in Helvetia fabricatum adhibetur ut elementum sensitivum pro experimento SF6 gasi compositionis productorum.Cum hardware professionalis xxxiii et praestantes algorithmorum STMicroelectronics programmatis, novam generationem 3-in-1 gasorum analystrorum produximus.
SF6Umor
●Modus mensurae: Resistiva et capacitiva mensurae principium
●Mensuratio range: ros punctum -80℃--+20℃(support ppmv)
●Sagaciter: ±1℃
(si ros punctum temperatus est infra 0℃, sensorem output est punctum pruinae)
●Responsio temporis: 63% [90%]
+20 →-20℃ Td 5s[45s]
-20 →-60℃ Td 10s[240s]
●Resolutio: 0.01℃
●Repetitio: ± 0.5
●Propono unitas: ℃, ppm, P20 (pretii 20 conversi)
●Gas fluunt: 400-600ml/min
●Flow display: 0-1000mL meter . digitales fluere
●Sample gas pressura: ≤1MPa
SF6Puritas
●Modus mensurae: Mensuratio Infrared Principii (seriem sensoriis NDIR)
●range mensurae: 0~ 100% SF6
●Responsio temporis: [90%] 60s
●Cura: ± 0.5% FS
●Repetitio: ± 0.5%
●Resolutio: 0.01%
●Propono unitas: %
SF6Decomposition Products
●Modus mensurae: Electrochemical Mensurae Principii (Series sensoriis Electrochemicae)
●Mensuratio range: H2S: 0 ~ 200ppmv
SO2: 0 ~ 200ppmv
CO: 0 ~ 500ppmv
HF: 0~50ppmv
●Sagaciter: H2S: 10ppmv±3%
SO2: 10ppmv±3%
CO: 50ppmv ± 4%
HF: 10ppmv±3%
●Repetitio: H2S: 10ppmv ± 2%
SO2: 10ppmv±2%
CO: 50ppmv±2%
HF: 10ppmv ± 2%
●Resolutio: 0.01ppmv
●Propono unitas: ppmv
●Potentiae copia: 220VAC±10%, 50Hz, AC/DC usus, tutela plus-custodia, operatio continua non minus quam 8hours.
●Uti environment temperatus: -20--+60℃
●Environment humiditas: XC% RH
●Mensurae valorem influxum: nullus effectus pressurae et fluxus
●Dimension: 395* 295* 155mm
●Pondus: de 2kg.
GDSF-411WPD SF6Decomposition Products
●Accuracy: H2S: <10ppmv ±0.3ppmv;>10ppmv±3%
SO2: <10ppmv ±0.3PPmv;>10ppmv±3%
●Repetitio: H2S: <10ppmv ±0.2ppmv;>10ppmv±2%
SO2: <10ppmv ±0.2PPmv;>10ppmv±2%
●Redivivus et implens munus: redivivus cubiculum 2L;redivivus tempus ≤ 5min
Cum Gas munus remittit
●Dimension: 395* 295* 315mm
●Pondus: de 5kg.
Principalis Tester | Pars I |
adaptor | 1 set |
Teflon pipe (includunt valvae fluxus commensuratio et iungo ieiunium) | 1 set |
Cauda tibia | 1 set |
Parce partes | 1 set |
Patina | Pars I |
User's Guide | Pars I |
Fama test | Pars I |